Mitsubishi Electric
NV30-FAU2P10A30
Moulded Case Circuit Breaker (MCCB) with embedded earth leakage protection / Earth Leakage Circuit Breaker (ELCB) - high-speed type - Mitsubishi (Japan series - Circuit Breakers for control panels - FAU series) - 2-poles (2P) - Rated current 10A - Residual current sensitivity 30mA - Short circuit current rating 2.5kA (240Vac; UL1077) - Thermal-Magnetic (fixed) trip unit - Front lugs or bars connection connection
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
NV30-FAU2P10A30
Online Price
$88.88
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
NV30-FAU2P10A30Mitsubishi Electric - Japan series - FAU series (Circuit Breakers for control panels)
Description
Moulded Case Circuit Breaker (MCCB) with embedded earth leakage protection / Earth Leakage Circuit Breaker (ELCB) - high-speed type - Mitsubishi (Japan series - Circuit Breakers for control panels - FAU series) - 2-poles (2P) - Rated current 10A - Residual current sensitivity 30mA - Short circuit current rating 2.5kA (240Vac; UL1077) - Thermal-Magnetic (fixed) trip unit - Front lugs or bars connection connection
Specifications
Primary brand
Mitsubishi
Main function
Moulded Case Circuit Breaker (MCCB) with embedded earth leakage protection / ELCB
Product series / family name
Japan series
Sub-range name
Circuit Breakers for control panels - FAU series
Functions
Moulded Case Circuit Breaker (MCCB) with embedded earth leakage protection / Earth Leakage Circuit Breaker (ELCB)
Design
high-speed type
Poles
2-poles (2P)
Rated current
10A
Trip current rating
10 AT
Frame current rating
30 AF
Residual current sensitivity
30mA
Rated voltage (AC)
240Vac (UL 1077)
Rated impulse voltage (Uimp)
2.5 kV
Connection type
Front lugs or bars connection
Short circuit breaking rating
2.5kA (240Vac; UL1077)
Trip unit type
Thermal-Magnetic (fixed)
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Earth leakage protection
Magnetic protection (Short-circuit)
Earth leakage protection
Protection settings
Thermal protection (Overload) -- tripping threshold fixed at 10A
Mounting mode
Surface mounting (or DIN rail with optional adapter)
Dimensions
W40mm x H72mm x D73.5mm
Manufacturer product status
Commercialized
Equivalent to
NV30FAU2P10A30
Rated Voltage (AC) - Phase-to-phase
230 V
Compliant with standard(s)
IEC 60947-2
EN 60947-2
UL 1077
CSA C22.2 No.235
GB14048.2
JIS C8201-2-2 Ann.1 Ann.2
TUV approval CE marking
CCC recognized
EN 60947-2
UL 1077
CSA C22.2 No.235
GB14048.2
JIS C8201-2-2 Ann.1 Ann.2
TUV approval CE marking
CCC recognized
Benefits
The UL 1077 MCCB and ELCB series "FAU" and "FHU" are suitable for the branch protection of the main single circuit of small or large control boards
Related Documents
Name | Last Update | Language |
---|---|---|
Mitsubishi - Circuit breaker Japan series - Singapore - Catalog.pdf | 26 Feb 2021 | English (US) |