Mitsubishi Electric
NF32-SVF3P5A
Moulded / Molded Case Circuit Breaker (MCCB) - Mitsubishi (Japan series - NF-S (standard class)) - 3-poles (3P) - Rated current 5A - Short circuit breaking capacity (Icu) 5kA (400Vac; IEC60947) - Thermal-Magnetic (fixed) trip unit - Front lugs or bars connection connection
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
NF32-SVF3P5A
Online Price
$152.51
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
NF32-SVF3P5AMitsubishi Electric - Japan series - NF-S (standard class)
Description
Moulded / Molded Case Circuit Breaker (MCCB) - Mitsubishi (Japan series - NF-S (standard class)) - 3-poles (3P) - Rated current 5A - Short circuit breaking capacity (Icu) 5kA (400Vac; IEC60947) - Thermal-Magnetic (fixed) trip unit - Front lugs or bars connection connection
Specifications
Primary brand
Mitsubishi
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Japan series
Sub-range name
NF-S (standard class)
Functions
Moulded / Molded Case Circuit Breaker (MCCB)
Poles
3-poles (3P)
Rated current
5A
Trip current rating
5 AT
Frame current rating
30 AF
Rated impulse voltage (Uimp)
6 kV
Rated insulation voltage (Ui)
440 V
Connection type
Front lugs or bars connection
Ultimate short circuit current breaking capacity (Icu)
10kA (125Vdc; IEC60947)
7.5kA (200Vac; IEC60947)
7.5kA (230Vac; IEC60947)
5kA (380Vac; IEC60947)
5kA (400Vac; IEC60947)
5kA (415Vac; IEC60947)
2.5kA (440Vac; IEC60947)
7.5kA (200Vac; IEC60947)
7.5kA (230Vac; IEC60947)
5kA (380Vac; IEC60947)
5kA (400Vac; IEC60947)
5kA (415Vac; IEC60947)
2.5kA (440Vac; IEC60947)
Service short circuit current breaking capacity (Ics)
10kA (125Vdc)
7.5kA (200Vac)
7.5kA (230Vac)
5kA (380Vac)
5kA (400Vac)
5kA (415Vac)
2.5kA (440Vac)
7.5kA (200Vac)
7.5kA (230Vac)
5kA (380Vac)
5kA (400Vac)
5kA (415Vac)
2.5kA (440Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
(400Vac) 100 %
Trip unit type
Thermal-Magnetic (fixed)
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Protection settings
Thermal protection (Overload) -- tripping threshold fixed at 5A
Mounting mode
Surface mounting (or DIN rail with optional adapter)
Dimensions
W54mm x H100mm x D90mm
Electrical durability (with load)
(440Vac) 6000 operations
Mechanical durability (at no load)
10000 operations
Utilisation category
A
Manufacturer product status
Commercialized
Equivalent to
NF32SVF3P5A
Compliant with standard(s)
IEC 60947-2
EN 60947-2
GB14048.2
JIS C8201-2-1 Ann.1 Ann.2
TUV approval CE marking
CCC recognized
EN 60947-2
GB14048.2
JIS C8201-2-1 Ann.1 Ann.2
TUV approval CE marking
CCC recognized
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|
Mitsubishi - Circuit breaker Japan series - Singapore - Catalog.pdf | 26 Feb 2021 | English (US) |