Mitsubishi Electric
NF32-SV3P8AMB
Thermal-Magnetic Motor Protection Circuit Breaker (MPCB) / Manual Mot. Protector Starter - Mitsubishi (WS-V series - NF-MB (motor protection)) - 3-poles (3P) - Rated current 8A - Rated power 3.7kW (400Vac-440Vac) - Short circuit breaking capacity (Icu) 5kA (400Vac; IEC60947) - Thermal-Magnetic (fixed) trip unit - Front lugs or bars connection connection
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
NF32-SV3P8AMB
Online Price
$84.84
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
NF32-SV3P8AMBMitsubishi Electric - WS-V series - NF-MB (motor protection)
Description
Thermal-Magnetic Motor Protection Circuit Breaker (MPCB) / Manual Mot. Protector Starter - Mitsubishi (WS-V series - NF-MB (motor protection)) - 3-poles (3P) - Rated current 8A - Rated power 3.7kW (400Vac-440Vac) - Short circuit breaking capacity (Icu) 5kA (400Vac; IEC60947) - Thermal-Magnetic (fixed) trip unit - Front lugs or bars connection connection
Specifications
Primary brand
Mitsubishi
Main function
Motor Protection Circuit Breaker (MPCB)
Product series / family name
WS-V series
Sub-range name
NF-MB (motor protection)
Functions
Thermal-Magnetic Motor Protection Circuit Breaker (MPCB) / Manual Mot. Protector Starter
Poles
3-poles (3P)
Rated current
8A
Trip current rating
8 AT
Frame current rating
30 AF
Rated power
3.7kW (400Vac-440Vac)
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
500 V
Connection type
Front lugs or bars connection
Ultimate short circuit current breaking capacity (Icu)
7.5kA (230Vac; IEC60947)
5kA (380Vac; IEC60947)
5kA (400Vac; IEC60947)
2.5kA (415Vac; IEC60947)
2.5kA (440Vac; IEC60947)
5kA (380Vac; IEC60947)
5kA (400Vac; IEC60947)
2.5kA (415Vac; IEC60947)
2.5kA (440Vac; IEC60947)
Service short circuit current breaking capacity (Ics)
7.5kA (230Vac)
5kA (380Vac)
5kA (400Vac)
2.5kA (415Vac)
2.5kA (440Vac)
5kA (380Vac)
5kA (400Vac)
2.5kA (415Vac)
2.5kA (440Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
(400Vac) 100 %
Trip unit type
Thermal-Magnetic (fixed)
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Protection settings
Thermal protection (Overload) -- tripping threshold fixed at 8A
Mounting mode
Surface mounting (or DIN rail with optional adapter)
Dimensions
W75mm x H130mm x D90mm
Electrical durability (with load)
(440Vac) 6000 operations
Mechanical durability (at no load)
10000 operations
Utilisation category
A
Manufacturer product status
Commercialized
Equivalent to
NF32SV3P8AMB
Compliant with standard(s)
IEC 60947-2
EN 60947-2
CE marking
Marine use approval NK; LR; ABS; GL
EN 60947-2
CE marking
Marine use approval NK; LR; ABS; GL
Benefits
The all-new "World Super V Series (WS-V Series)" built with a new breaking technology is designed to respond to the individual market needs of the receiving and distribution and machineries.
This series is the result of revolutionary evolution
Equipped with a new cutoff technology to enhance interrupting performance
Compatible with the latest standards of various countries to deliver optimal performance according to individual needs.
This series is the result of revolutionary evolution
Equipped with a new cutoff technology to enhance interrupting performance
Compatible with the latest standards of various countries to deliver optimal performance according to individual needs.
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|
Mitsubishi Electric - WS Series Circuit Breakers - Catalog.pdf | 14 Jul 2022 | English (US) |
Mitsubishi - Low-voltage power distribution products - Catalog.pdf | 26 Feb 2021 | English (US) |