MMP-T32BCLF 18A
Thermal-Magnetic Motor Protection Circuit Breaker (MPCB) / Manual Mot. Protector Starter - Mitsubishi (WS-V series - MMP-T Motor Circuit Breakers) - 3-poles (3P) - Rated current 18A - Short circuit breaking capacity (Icu) 50kA (400Vac; IEC60947) - Thermal-Magnetic (adjustable) trip unit - Screw-clamp connection
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
MMP-T32BCLF 18A
Online Price
$63.63
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
MMP-T32BCLF 18AMitsubishi Electric - WS-V series - MMP-T Motor Circuit Breakers
Description
Thermal-Magnetic Motor Protection Circuit Breaker (MPCB) / Manual Mot. Protector Starter - Mitsubishi (WS-V series - MMP-T Motor Circuit Breakers) - 3-poles (3P) - Rated current 18A - Short circuit breaking capacity (Icu) 50kA (400Vac; IEC60947) - Thermal-Magnetic (adjustable) trip unit - Screw-clamp connection
Specifications
Primary brand
Mitsubishi
Main function
Motor Protection Circuit Breaker (MPCB)
Product series / family name
WS-V series
Sub-range name
MMP-T Motor Circuit Breakers
Functions
Thermal-Magnetic Motor Protection Circuit Breaker (MPCB) / Manual Mot. Protector Starter
Poles
3-poles (3P)
Rated current
18A
Trip current rating
18 AT
Frame current rating
32 AF
Rated operating voltage (Ue)
200-690 V
Rated impulse voltage (Uimp)
6 kV
Rated insulation voltage (Ui)
690 V
Connection type
Screw-clamp
Ultimate short circuit current breaking capacity (Icu)
100kA (200Vac; IEC60947)
100kA (240Vac; IEC60947)
50kA (400Vac; IEC60947)
50kA (415Vac; IEC60947)
35kA (440Vac; IEC60947)
35kA (460Vac; IEC60947)
10kA (500Vac; IEC60947)
4kA (600Vac; IEC60947)
4kA (690Vac; IEC60947)
100kA (240Vac; IEC60947)
50kA (400Vac; IEC60947)
50kA (415Vac; IEC60947)
35kA (440Vac; IEC60947)
35kA (460Vac; IEC60947)
10kA (500Vac; IEC60947)
4kA (600Vac; IEC60947)
4kA (690Vac; IEC60947)
Service short circuit current breaking capacity (Ics)
100kA (200Vac)
100kA (240Vac)
38kA (400Vac)
38kA (415Vac)
27kA (440Vac)
27kA (460Vac)
8kA (500Vac)
3kA (600Vac)
3kA (690Vac)
100kA (240Vac)
38kA (400Vac)
38kA (415Vac)
27kA (440Vac)
27kA (460Vac)
8kA (500Vac)
3kA (600Vac)
3kA (690Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
(400Vac) 76 %
Trip unit type
Thermal-Magnetic (adjustable)
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Protection settings
Thermal protection (Overload) -- adjustable tripping threshold 12A...18A
Mounting mode
Surface mounting (or DIN rail with optional adapter)
Electrical durability (with load)
100000 operations
Mechanical durability (at no load)
100000 operations
Utilisation category
AC-3
Manufacturer product status
Commercialized
Equivalent to
MMPT32BCLF18A
Compliant with standard(s)
IEC 60947-2
IEC 60947-4-1
EN 60947-2
EN 60947-4-1
GB14048.2
JIS C8201-2-1 Ann.1
JIS 8201-4-1
IEC 60947-4-1
EN 60947-2
EN 60947-4-1
GB14048.2
JIS C8201-2-1 Ann.1
JIS 8201-4-1
Benefits
Protects failure of the industrial motor by means of a single device One Motor Circuit Breaker can detect overload operation and phase-loss operation of a motor and also makes it possible to cut off short-circuit current.
This compact body Motor Circuit Breaker achieves a rated short-circuit breaking capacity of 100kA (200/240V).
Improves safety during product maintenance
The Motor Circuit Breaker is provided with a DIN and VDE standards-compliant charging part protection cover as standard.
This cover helps to improve safety during maintenance work.
Reduces the size of the control board and distribution board The internal structure of the Motor Circuit Breaker has been optimized to reduce depth.
When a connection conductor unit (UT-MT) is used it will further reduce the size of the control board and distribution board.
it can be assembled with an auxiliary contact/alarm contact unit as well as a short-circuit indicator unit (displays in red when short-circuit occurs) in a 45mm-width body.
This compact body Motor Circuit Breaker achieves a rated short-circuit breaking capacity of 100kA (200/240V).
Improves safety during product maintenance
The Motor Circuit Breaker is provided with a DIN and VDE standards-compliant charging part protection cover as standard.
This cover helps to improve safety during maintenance work.
Reduces the size of the control board and distribution board The internal structure of the Motor Circuit Breaker has been optimized to reduce depth.
When a connection conductor unit (UT-MT) is used it will further reduce the size of the control board and distribution board.
it can be assembled with an auxiliary contact/alarm contact unit as well as a short-circuit indicator unit (displays in red when short-circuit occurs) in a 45mm-width body.